Chapter 1 Introduction
Smart Grid Construction is growing rapidly, so smart meters have been installed in residential areas to collect a large amount of data on voltage, current, power and energy use in a more fine-grained way [10]. The measurement data of the smart meter will be sent up through the local communication module, the central data collector and the wide-area channel, and then sent to the master station for billing, load forecasting and anomaly diagnosis [1]. But because of channel congestion, electromagnetic interference, terminal failure and unstable wireless links, there will be a certain amount of packet loss in the data transmission process, reducing the completeness of the data and thus affecting the reliability of subsequent analysis applications [7]. Therefore, it is necessary to study the regularity of packet loss in terms of statistics and the stability of the acquisition process, which is an important problem in theory and practice.
The packet loss rate is the number of lost data packets in a certain period of observation and is often used to characterise the degree of data loss in this study. The state of the data will change over time, be different in different areas and have random fluctuations; all these need to be studied through systematic field measurements and statistical modelling. A thorough examination of collection stability should first be carried out to clarify the entire data chain, determine the main reasons for data loss at each stage, and set up repeatable experimental methods for long-term observation under various loads and environments [4].
This paper's research has made two important contributions. In terms of academic research, it has added to the body of knowledge on how communication reliability changes in low-voltage distribution networks and served as the basis for fitting loss rates and stability indicators. Based on the regularity of packet loss, it can help us design better retransmission strategies, repair methods and the deployment of collectibles to improve the accuracy of the settlement-grade metering data and the working level of the utility information system [13]. Therefore, this paper will take the residential distribution room as the object of investigation, build a multi-dimensional collection and analysis system, and systematically investigate the stability of smart meter data packets, thus laying a foundation for the subsequent modelling and verification work in the following chapters.
Chapter 2 Analysis of Data Packet Loss Patterns and Collection Stability in Residential Distribution Room Smart Meters
2.1 Overview of Smart Meter Data Collection Architecture and Packet Loss Mechanisms
2.1.1 Communication Links and Data Transmission Paths in Residential Distribution Rooms
The data collection architecture of the smart meters in the residential distribution room is hierarchical and has three levels. The bottom layer is the sensing terminal of the smart meter at each household, which is in charge of energy metering and data storage. The middle layer consists of collection concentrators (data collection terminals) placed in the distribution room that collect meter data and have a small amount of local storage. The top layer is a master station system that can perform functions such as unified scheduling, data management and analysis. As a result of the hierarchical organisation, data will have to pass through several communication links before reaching the master station; therefore, there is a possibility of packet loss at each link.
The communication links can be divided into two types. The local line connecting the meter to the concentrator may be a low-voltage power line carrier (PLC) or an RS-485 wired bus. PLC is widely used because no extra wiring is required, but its transmission quality is easily affected by load noise, impedance mismatch and channel attenuation in low-voltage distribution networks; thus, it is the part most likely to experience packet loss. RS-485 has a good transmission stability, but it is vulnerable to wiring faults and electromagnetic interference. Remote channels connect the concentrator to the master station through GPRS/4G cellular networks, NB-IoT, or optical fibre. The wireless remote channels may experience issues such as signal fading, base station congestion and shadow areas of coverage; fibre links are relatively stable.
The whole reading procedure is as follows: the master station will send a reading instruction to the concentrator by remote channel; the concentrator will send the request to the target meters via local channel; the meters will send the data frame in the opposite direction; and the concentrator will finally send the data to the master station. Command issuance, carrier transmission, meter response and upstream reporting may experience data loss due to channel errors, buffer overflow or node failure. At the protocol level, the communication protocols for metering often adopt a stop-and-wait mode; that is to say, when the receiving node does not receive an ACK in the time-out range, it will resend the frame. Packet loss will occur after too many retransmissions, and thus reduce the completeness and stability of collection; therefore, this study is aimed at the problem of packet loss.
2.1.2 Classification of Packet Loss Causes: Channel Interference, Network Congestion, and Terminal Faults
To accurately assign responsibility for packet loss, we need to have a good classification of why packets are lost, and the main reasons are usually the first three, namely channel interference, network congestion and terminal faults.
Low-voltage power line carrier (PLC) communication is often subject to channel interference. Noise sources in the 220 V distribution network are switching power supplies, frequency converters, and household appliances such as air conditioners, induction cookers, etc., that release broadband impulse and cyclostationary noise into the carrier band. In wireless micro-power communication, there is adjacent-channel interference and co-channel occupation by neighbouring collection systems; therefore, there is a similar level of degradation. Interference can increase the bit error rate at the physical layer; once the BER exceeds the correction ability of forward error coding, the frame will not pass the cyclic redundancy check and will be dropped, which is called frame loss at higher protocol layers. The characteristics of signature are that packet loss occurs at a certain time when the appliances are in high demand, and it does not tend to be concentrated in a few places.
Network congestion is the reason why many meters share a limited bandwidth in the uplink of the concentrator. There are thousands of metering frames competing for the channel at regular time during the daytime to collect data, and thus congestion will be experienced at the concentrator or its communication module due to a queue of too many frames. Congestion loss is regular over time; the rate of loss will rise at the start of the collection window, decrease as the queue is filled up, and at the same time, the rate of retransmission will increase in the logs.
A terminal fault is a problem with the meter or concentrator. Degradation of the power line coupling circuit and communication module caused by hardware aging is one cause; power supply interruption, module failure, and solder joint deterioration are also reasons for the inability to connect. Software anomalies such as program crashes, memory leaks, and abnormal restarts can lead to data loss; once the device is restarted, the data loss is no longer severe. Fault-induced packet loss is not random, but rather device-dependent in nature, and the occurrence of consecutive failures of the same meter address in different collection periods is frequently observed in logs; upon resetting, the loss will cease. The above three types of packet loss are mapped to their respective observation behaviours in the collection log, and on this basis, the reasons for the measured packet loss in the next part of this paper are analysed.
2.2 Statistical Characterization of Packet Loss Patterns
2.2.1 Temporal Distribution of Packet Loss: Peak-Off-Peak and Diurnal Variations
The time distribution of packet loss is one of the basic characteristics of statistics, and the collection failures in the distribution room of a residential area are not evenly spread throughout the day. In this paper, the historical collection records of a year were collected at three levels: hour, day and month, and a hierarchical picture of temporal dependence was created. At the hourly level, the packet loss rate is calculated as the ratio of the number of failed data reads to the number of attempts within each one-hour slot; the daily and monthly aggregates will also be used to smooth out stochastic fluctuations and show trends over a longer period.
The diurnal variation curves show a clear bimodal shape. The evening residential load peak is usually around 18:00 to 22:00, and at this time, the packet loss rate increases significantly; the peak-to-valley ratio is about 2.8 compared to the nocturnal baseline from 01:00 to 05:00. A second elevation appears at the time of the Centralized Collection Window in the master station, usually in the early morning, when all the meters in a large area of a transformer district are connected at the same time. This concurrency will occupy the uplink bandwidth and the processing capability of the concentrator quickly, resulting in congestion-induced retransmissions and timeouts. However, at night, due to low channel contention and less switching load electromagnetic interference, the collection performance is better.
Further division based on the type of day shows that there is about a 12 percent more loss on weekdays than on weekends, which is in line with the higher load activity and more frequent metering traffic on weekdays. In order to determine whether these patterns are regular or not due to random fluctuations, an autocorrelation analysis of the hourly loss series was carried out; it was found that there was a significant positive autocorrelation at 24 and 168 hours, corresponding to daily and weekly periodicities, respectively. The chi-square goodness-of-fit test for the number of losses in each hour bin showed that the hypothesis of time homogeneity could be rejected at the 0.01 level of significance. The above results show that packet loss is caused by regular load and schedule fluctuations, and they provide a statistically strong foundation for constructing an adaptive collection schedule.
2.2.2 Spatial Distribution of Packet Loss: Concentrator Coverage and Meter Location Effects
Spatial distribution of packet loss is one of the key reasons for the poor collection stability of low-voltage smart meter; the communication faults that occur in these networks are usually not randomly distributed in space, but will be concentrated in certain areas. Therefore, we have allocated all of the packet loss events that have occurred during the observation period to the specific meter positions in the studied residential area; thus, there is a map of the geographical coordinates of each meter, its affiliated concentrator, and the measured loss rate. Therefore, the observed variations can be attributed to the quality of coverage provided by each data collection terminal and the installation environment of the meter.
First, compare the loss rate distribution of each concentrator. For each concentrator, calculate the average loss rate, variance and maximum value of all the subordinate meters to show that the inter-concentrator variance is much larger than the intra-concentrator variance. Therefore, the packet loss at the concentrator level is mainly caused by changes in the characteristics of the transmit power, uplink channel quality and local interference in the system. However, in the area covered by one concentrator, there is still a large spatial difference in the loss rate; meters that are far away from the concentrator or have many hops in the power-line-carrier route will have higher loss rates due to signal attenuation and unstable routing over long-distance carrier paths.
The installation environment of the meter also has an effect on this phenomenon. The loss rate of a meter installed in a basement or cable shaft is higher than that of one placed in an indoor distribution box; this difference is due to the fact that reinforced concrete can better block signals, moisture in the environment is more severe, and the metal enclosure will attenuate the carrier wave and micro-wireless signals. In addition, the meters that are in the coverage area at the edge of the concentrator will have a high concentration of loss, which is due to the marginal signal-to-noise ratio and frequent reconfigurations of the route.
Based on statistics, one-way ANOVA was used to compare the distributions of loss per concentrator, and it has been found that there is a significant difference between groups at the 0.05 level. By visualising the high-loss meters in the residential area with a heat map, it can be found that these high-loss nodes are concentrated in the boundary areas and underground facilities. The above results show that the two main causes of packet loss are communication distance and physical installation environment; therefore, the subsequent discussion on the optimisation of concentrator locations will be based on this evidence.
2.2.3 Correlation between Packet Loss Rate and Environmental/Load Factors
To quantify how packet loss behavior changes with the external operating environment, a number of explanatory variables are selected for this paper, including both electrical load and the environment. The load-related variables are the instantaneous load current at the distribution room feeder and the transformer load rate, i.e., the actual apparent power divided by the rated capacity. The Environment variables are the ambient temperature, relative humidity and rain, thunderstorm etc., which are binary indicators for regression. Packet loss rate is the ratio of lost to expected uplink data frames in each 15-minute collection window, and it will be used as the response variable in this analysis.
Pearson's correlation coefficient is calculated first for each continuous variable and the observed packet loss rate to find the linear correlation. Then, a lagged correlation analysis and a multiple linear regression are done to take into account the delayed effects; thunderstorm-induced electromagnetic interference or humidity-driven signal attenuation could cause a time lag of several minutes to affect communication quality. An important issue in the study of this method is distinguishing between actual causal influence and other reasons due to the time of day: both load current and packet loss rate have obvious daily changes that increase in the evening when the residential use of electricity is high and network traffic is heavy. Partial correlation analysis with the hour-of-day variable is carried out to separate the remaining correlation caused by the factors themselves.
The results show that Transformer load rate and Thunderstorm frequency have the greatest explanatory power among all variables, and they can account for the majority of the variance in the packet loss rate, while Temperature has little marginal effect after removing the diurnal confounding. Humidity has a relatively high positive correlation, especially in the period of continuous rain. The above conclusions show that large loads and bad weather are the main reasons why collection reliability declines; thus, a basis for prioritising stability improvement measures to reduce load and communication redundancy in bad weather can be obtained.
2.3 Evaluation of Collection Stability
2.3.1 Stability Metrics: Success Rate, Retry Rate, and Data Completeness
To quantitatively describe the stability of the smart meter that has been installed in the living distribution room, in this paper, a three-level index system of data collection success rate, retry rate, and data completeness rate has been constructed. These indicators cover the entire chain from a single reading operation to the end of the cycle of data availability, and can be used to evaluate stability hierarchically.
The data collection success rate is the ratio of the number of frames that have been successfully read to the total number of read frames issued in a certain period; that is to say, R_success = N_read / N_issue × 100%, in which N_read is the number of frames with valid checksums and correct address verification, and N_issue is the number of frames issued by the collector or master station. The data are obtained from the communication logs of the concentrator and the master station's collection platform. Usually, the daily statistical window is used to calculate this index; according to the rules of industry-based assessment, a rate of 99% or more is considered excellent, 97% to 99% is qualified, and less than 97% is unqualified.
The retry rate is the degree of retransmission and is calculated by R_retry = N_retry / N_total × 100%, in which N_retry is the number of retransmission attempts due to timeouts or checksum errors, and N_total is the total number of transmission attempts. The frame counter is in the communication record of the acquisition platform. Because many retries happen before outright read failures, it can also be used for early warning; a rate below 5% is excellent, between 5% and 10% is good, and above 10% is bad, and it is better to use a monthly window for the data to eliminate short-term fluctuations.
The data completeness rate is used to examine the availability of billing-relevant data in the settlement cycle, that is, how much of the required data for billing has been successfully obtained, and the formula is R_complete = M_obtained / M_required × 100%, where M_obtained is the number of successfully obtained data items such as daily frozen load curves and forward active energy registers, and M_required is the number of items in the required collection plan per billing cycle. It is calculated monthly from the master station's database. Generally, the thresholds are set to ≥99.5% (excellent), 98%–99.5% (qualified), and <98% (unqualified).
The above indicators are not isolated, they are related to each other. A high success rate may also be accompanied by a high retry rate, and it may be due to hidden channel degradation; otherwise, the completeness will be based on how many successful and retry attempts have been made over time. The main problem is that the total ratio is not able to identify the specific reason for the failure, so some other kind of diagnostic analysis needs to be done. At the same time, the three indicators also offer a basis for comprehensive and verifiable stability assessment.
2.3.2 Comparative Stability Assessment under Different Communication Modes
To study the impact of communication mode on Collection Stability systematically, this section will compare the three indicators of Collection Success Rate, Retry Rate, and Data Completeness for Meter Groups using different local and remote communication technologies. For local channels, low-voltage power line carrier (PLC) and micro-power wireless (470 MHz) will be used at the same concentrator, meter, and schedule with the same load profile; for remote channels, GPRS/4G cellular uplinks will be compared with NB-IoT and optical fiber under the same Concentrator and scheduling system.
The statistical analysis will be done in three parts. Firstly, the three indicators for each meter group and time period will be calculated according to the formula in Section 2.3.1 using the raw reading data, and at least thirty consecutive days should be taken to reduce the influence of short-term fluctuations. Then, create a grouped comparison table and bar or box chart to show the central tendency and dispersion of each index in different modes. Finally, Hypothesis testing will be employed to determine whether the differences in observed values are statistically significant, and a Two-sample t-test or Mann-Whitney U test will be chosen based on the normality test (Shapiro-Wilk). Levene's Test will be applied before a test for homogeneity of variance; a significance level of 0.05 is adopted throughout.
Based on the above data, it can be concluded that Micro-power wireless has higher success rates (above 99%) and fewer retries than PLC; however, PLC is significantly affected in cases of heavy nonlinear loads or poor channel impedance, and thus has relatively weak anti-interference ability despite not requiring extra spectrum. NB-IoT has similar success rates and completeness to Fiber in a dense residential area for remote channels, and is better than GPRS/4G in a basement distribution room due to its good Link-budget penetration; nevertheless, its narrow bandwidth cannot support high-frequency reading tasks in real time, so Fiber is still better.
According to the comparison, the communication mode is one of the primary factors that affect the stability of collection. Therefore, the mode selection should be based on different situations; for instance, if the base stability of the meter group is over 98%, micro-power wireless or strong PLC with mesh relay will be employed; otherwise, NB-IoT will be used in general for reading daily data in a signal-reduced environment; otherwise, fibre will be used by the concentrator that needs millisecond-level real-time performance and large-volume data backhaul.
Chapter 3 Conclusion
This paper will examine in detail the packet loss problem of smart meter data collection in a residential distribution room, mainly focusing on how well the collection process operates under various operating conditions. Based on a measurement system that contains deployed data acquisition terminals, set statistically designed sampling windows and quantifiable stability indicators, the research has determined a repeatable way to describe the phenomenon of packet loss instead of regarding it as an accident [15]. According to the experimental results, there are specific rules in the packet loss related to transmission load, communication channel quality, terminal polling cycle and metering side response latency; thus, it can be modelled and predicted rather than just observed.
From the point of engineering, the main result is to construct a stability assessment index that takes the average loss rate of an instant and its variance over several collection cycles. The dual-criterion approach can identify the temporary faults that are self-recovering and allowable for operation, as well as the continuous degradation that indicates hardware ageing, signal interference or configuration error [9]. According to the test results of typical residential distribution rooms, the new index is sensitive to minor interference and does not respond to minor fluctuations, providing useful information for operators of the system and managers to prepare in advance.
The practical effects are three in number. According to the loss rate determined, it can provide a basis for condition-based maintenance scheduling, reduce unnecessary on-site inspections and avoid prolonged data gaps that affect billing accuracy and load forecasting [12]. Second, the correlation analysis between polling strategy and loss behaviour can guide how to adjust the collection frequency and timeout parameters in the terminal [6]. Third, the statistical characterisation of diurnal and seasonal changes in packet loss provides a quantitative basis for the expansion of low-voltage communication networks in residential areas [3].
However, there are some shortcomings in the study. The sample of distribution rooms is representative in number but limited to a certain area geographically; the problem of long-term aging of the components has not been studied for a long time. Future work will expand the framework to include heterogeneous metering architectures, introduce adaptive retransmission mechanisms based on the observed loss laws, and verify the stability index in various network topologies to enhance the generalisation and practicality of the results in industry.
References
[1]杨继革, 严俊, 陈丽春. 基于智能电表的住宅短期电力负载预测[J]. 沈阳工业大学学报, 2022, 44(3): 255-258.
[2]黄一凡, 郭鹏, 朱彦鸣. 基于西门子PLC的智能电表电能数据采集方法研究[J]. 锻压装备与制造技术, 2026, 61(3): 81-87.
[3]吕玉玲, 陈文礼, 程瑛颖. 基于约束优化模型的智能电表运行误差及日线损率联合估计方法[J]. 电网技术, 2025, 49(3): 1257-1265.
[4]任梓豪, 张苏敏. 智能电表数据采集标准化管理技术研究[J]. 中国标准化, 2026(S2): 101-103.
[5]周润, 向月, 王杨. 基于智能电表集总数据的家庭电动汽车充电行为非侵入式辨识与负荷预测[J]. 电网技术, 2022, 46(5): 1897-1906.
[6]王海童, 于洪旺, 柴园园. 基于数据驱动的配电网拓扑参数辨识方法[J]. 河北工业大学学报, 2026, 55(4): 65-74.
[7]江剑峰, 李蕊, 周菁菁. 智能电表批次故障预警系统研究[J]. 电气自动化, 2025, 47(4): 92-95+99.
[8]Jaime Lloret, Jesús Tomás, Alejandro Cánovas. An Integrated IoT Architecture for Smart Metering[J]. IEEE Communications Magazine, 2016.
[9]Chih‐Che Sun, D. Jonathan Sebastian-Cardenas, Adam Hahn. Intrusion Detection for Cybersecurity of Smart Meters[J]. IEEE Transactions on Smart Grid, 2020.
[10]Matteo Orlando, Abouzar Estebsari, Enrico Pons. A Smart Meter Infrastructure for Smart Grid IoT Applications[J]. IEEE Internet of Things Journal, 2021.
[11]Lalitha Sankar, Siva Raj Rajagopalan, Soheil Mohajer. Smart Meter Privacy: A Theoretical Framework[J]. IEEE Transactions on Smart Grid, 2012.
[12]Andrew J Berrisford. Smart Meters should be smarter[J]. IEEE Power and Energy Society General Meeting (PESGM), 2012.
[13]Dong Chen, Sean Barker, Adarsh Subbaswamy. Non-Intrusive Occupancy Monitoring using Smart Meters[J]. 2013.
[14]A. Alimardani, Francis Therrien, Djordje Atanackovic. Distribution System State Estimation Based on Nonsynchronized Smart Meters[J]. IEEE Transactions on Smart Grid, 2015.
[15]Yi Wang, Qixin Chen, Tao Hong. Review of Smart Meter Data Analytics: Applications, Methodologies, and Challenges[J]. IEEE Transactions on Smart Grid, 2018.